| 1.1 |
Surface Preparation |
Substrate Cleaning, Tie-Rod Cone Grouting & Sharp Protrusion Grinding |
H
W
R
|
BS 8102 / ASTM D4258 |
Surface smooth, free of fins, honeycombs, grease and dust; tie-rod holes plugged with non-shrink mortar |
Civil QC Inspector |
| 1.2 |
Surface Moisture |
Concrete Substrate Moisture Content Test Prior to Priming |
H
W
S
|
ASTM D4263 (Plastic Sheet Method) |
Moisture content <= 4% using calibrated moisture meter or zero condensation under 24h taped polyethylene |
Waterproofing Specialist & QC |
| 2.1 |
Corner Detailing |
Installation of 50x50mm Angle Fillets (Cants) at All Wall-to-Floor Junctions |
H
W
S
|
Manufacturer Specification |
Continuous 50mm mortar chamfer at all 90° internal corners to prevent membrane stress tears |
Waterproofing Foreman & QC |
| 2.2 |
Primer Application |
Bituminous Primer Application Coverage & Drying Time Verification |
W
W
S
|
ASTM D41 |
Uniform coverage >= 0.25 lit/m²; completely tack-free and dry before membrane torching commences |
Waterproofing Inspector |
| 2.3 |
Membrane Torching |
SBS/APP Modified Bituminous Membrane (4mm) Torch-Welding & Alignment |
H
H
W
|
ASTM D6163 / ASTM D6164 |
Membrane fully bonded with continuous bitumen bleed-out along edge; zero air bubbles, wrinkles or bridging |
Waterproofing Specialist & QC |
| 2.4 |
Laps & Seams |
Side Lap (100mm) and End Lap (150mm) Heat Sealing & Trowel Pressing |
H
H
W
|
ASTM D6163 Section 7 |
Side laps >= 100mm, end laps >= 150mm; seams sealed and chamfered with heated trowel; zero unbonded flaps |
Waterproofing QC & Consultant |
| 2.5 |
Pipe Penetrations |
Flashing Sleeves, Double Membrane Reinforcement & Clamping Rings |
H
H
W
|
Approved Waterproofing Detail |
Pipe wrapped with two extra collar layers extending 150mm up pipe; stainless steel jubilee clip clamped |
Civil QA/QC & Consultant RE |
| 3.1 |
Quality Verification |
48-Hour Water Flood Testing for Roof Slabs & Balconies |
H
H
H
|
ASTM D5957 |
Standing water maintained at 50mm depth for 48 hours; zero dampness, damp stains, or leaks on soffit underside |
Contractor QC, Consultant & Client |
| 3.2 |
Protection |
Protection Board (Bituboard) or Dimpled Drainage Sheet Installation |
H
W
S
|
Project Technical Specs |
3.2mm asphaltic protection board bonded immediately over membrane before soil backfilling operations |
Civil Foreman & QC Inspector |